1-23911-K085DK
FireBeta XT+ Extinguishing Control Panel (4 Zone / 2 Area)
- EN12094-1, EN54-2 and EN54-4 approved
- Four detection zones and 2 extinguishing areas as standard
- Dual configurable extinguishing outputs as well as first and second stage sounder outputs for each area
- First and second stage potential free changeover contacts for each area
- Agent released and common fault potential free contact per area
Alternative produkter
Overblik
General
The FireBeta XT (4 Zone / 2 Area) is a multi-area extinguishing control panel complying with EN12094-1, EN54-2 and EN54-4. It offers 4 detection zones for controlling 2 extinguishing areas.
Each extinguishing area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface. All extinguishing areas may have up to 7, serially connected status indication and control units connected via a simple 4 core cable.
The versatility of the control panel may be further enhanced by the fitting up to 7 ancillary or sounder boards to the RS485 serial bus.
Detaljer
- EN12094-1, EN54-2 and EN54-4 approved
- Four detection zones and 2 extinguishing areas as standard
- Dual configurable extinguishing outputs as well as first and second stage sounder outputs for each area
- First and second stage potential free changeover contacts for each area
- Agent released and common fault potential free contact per area
- Programmable extinguishing delays and output duration
- Extract fan control
- A countdown indicator shows the time in seconds until release
- Mode select and manual release controls per area
- Monitored remote inputs for manual release, hold, mode select (door interlock), released pressure switch, and low pressure switch
- Monitored abort input
- Serial connection for status units and ancillary boards
Tekniske specifikationer
| General | ||
|---|---|---|
| Status indicaton |
LEDs & countdown timer
|
|
| Compatibility |
Status unit/Ancillary board connection
|
|
| Connectivity |
Two wire RS485
|
|
| Communication ports |
1
|
|
| Maximum system capacity (device count) |
up to 128
|
|
| Network size (nodes) |
up to 8
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
230 VAC
|
|
| Power consumption |
100 W (max.)
|
|
| Operating voltage |
28 VDC ±2 V
200 mV (Maximum ripple)
|
|
| Current consumption |
0.095 A
1.6 A (Mains fuse rating)
|
|
| Power supply rating | 3 A | |
| Zone | ||
|---|---|---|
| Maximum zone capacity |
up to 4
|
|
| Operating voltage |
21 to 28 VDC
|
|
| Quantity of devices per zone |
32 (max.) type dependent, typically 20
|
|
| Cable rating |
0.5 mm² to 2.5 mm² solid or stranded wire, FP200 or equivalent (max capacitance 1µF max inductance 1 mH)
|
|
| Quiescent current | 2 mA (max.) | |
| Termination | 6k8 ½ W | |
| Thresholds | Normal, 10 to 2 kΩ | |
| Thresholds | Detector alarm, 1000 to 390 Ω | |
| Thresholds | Manual call point alarm, 370 to 150 Ω | |
| Thresholds | Short circuit, 130 to 0 Ω | |
| Input | ||
|---|---|---|
| Input quantity |
4
|
|
| Input type and rating |
SIL, AL, FLT, RST switched -ve 100 Ω
|
|
| Programmable |
Yes
|
|
| Termination |
6k8 ½ W
|
|
| Thresholds | Normal, 10 to 2 kΩ | |
| Thresholds | Alarm, 2000 to 150 Ω | |
| Thresholds | Short circuit, 140 to 0 Ω | |
| Output | ||
|---|---|---|
| Output quantity |
13
|
|
| Output type and rating |
Output specific
|
|
| Fire alarm signalling |
1 A @ 30 VDC
|
|
| Fault signalling |
1 A @ 30 VDC
|
|
| Notification |
1 A @ 21 to 28 V
|
|
| Auxilliary power |
500 mA @ 24 V
|
|
| Programmable |
Yes
|
|
| Termination |
Output specific
|
|
| Output type and rating | Local fire relay, 1 A @ 30 VDC | |
| Output type and rating | 1st stage relay, 1 A @ 30 VDC | |
| Output type and rating | 2nd stage relay, 1 A @ 30 VDC | |
| Output type and rating | Extract fan, 1 A @ 30 VDC | |
| Output type and rating | Extinguishing release, 1A @ 21 to 28 VDC | |
| Output type and rating | Status unit, 500 mA @ 21 to 28 VDC | |
| Extinguishing release delay | 0 to 60 s (5 s steps) | |
| Extinguishing release duration | 60 to 300 s (5 s steps) | |
| Termination | Notification, 10K ¼ W | |
| Termination | Extinguishing, 1N4004 | |
| Standby battery | ||
|---|---|---|
| Capacity |
2 x 12 V, 7 Ah, Yuasa NP SLA
3.15 A (Battery fuse rating)
3 A (max. Baterey current)
|
|
| Charging |
0.7 A @ 27.6 VDC (temperature compensated)
|
|
| Batteries supported in housing |
2
|
|
| Colour code | BS 00 A 05 | |
| Physical | ||
|---|---|---|
| Form factor |
Wall mount
|
|
| Physical dimensions |
385 x 520 x 110 mm
|
|
| Net weight |
8 kg
|
|
| Colour |
Grey
|
|
| Mounting type |
Wall mount
|
|
| Material | Mild sheet steel (1.2 mm) | |
| Finish | Epoxy powder coated | |
| Terminal capacity | 12 AWG | |
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Environment |
Indoor
|
|
| IP rating |
IP30
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
REACH
RoHS 2
WEEE
|
|
| Certification |
EN12094-1
EN54-2
EN54-4
|
|
Downloads
All downloadsDatablad
Certificaten
Hvis de er tilgængelige, vises downloads af certifikater, software og firmware og medier på deres standardsprog.