NC-DPM-W
Conventional multisensor fire detector (White)
- Supports drift compensation to enable good environmental adaptability
- Self-diagnostic
- Local test activation with reed switch
- Chamber contamination checking
- All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
Related products
At a glance
General
The DC-9101E combines photoelectric (optical) detection, fixed temperature and rate-of-rise detection technology. The smoke and heat sensors are integrated to provide a solution to a wide range of applications, allowing detecting of more complex fire types. Amongst these include are fire types generating black smoke as well as small particles fires such as those from burning alcohol.
Application
The detector supports installation on the GST DB-01 conventional detector base for standard applications, or the GST DB-01D diode base when head-out functionality to BS5839 standard is required. Detection sensitivities are programmable using the GST P-9910B device programmer.
Details
- Supports drift compensation to enable good environmental adaptability
- Self-diagnostic
- Local test activation with reed switch
- Chamber contamination checking
- All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation
- Configurable polling LED support
- Remote indicator output
- 2 Programmable smoke sensitivity levels
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Red LED
|
|
| User interface |
Via LED - polling, fault, contamination and alarm
|
|
| Compatibility |
GST100A Series conventional CIEs as well as GST I-9319 Zone Monitor
|
|
| Reset voltage |
<1 VDC
|
|
| Reset time |
<10 s
|
|
| Alarm levels |
2
|
|
| Connectivity |
Zone connection - 2-core (polarity sensitive), RI connection - 2-core (polarity sensitive)
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
9.5 to 28 VDC (24 VDC typical)
|
|
| Current consumption |
<60 μA (Quiescent)
≤55 mA (Alarm)
|
|
| Cable specification |
>1.0 mm²
|
|
| No. of cable cores |
2
|
|
| Terminals |
4
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Optical & Heat
|
|
| Sensitivity |
Programmable
|
|
| Zone length |
Panel dependent
|
|
| Heat Class | A2R | |
| Activation temperature | 62°C | |
| Output | ||
|---|---|---|
| Remote alarm output |
1
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
54.5 mm (including base) x 100 mm Ø
|
|
| Net weight |
±110 g
|
|
| Colour |
Traffic white (RAL9016)
|
|
| Mounting type |
Ceiling mount
|
|
| Material (body) |
ABS
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +50°C
|
|
| Relative humidity |
0 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP2x
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
WEEE
|
|
| Certification |
EN54-5
EN54-7
|
|
| Voluntary marks |
BOSEC
|
|
| Standards |
LPCB
|
|
Downloads
All downloadsDatasheet
CPD / CPR
Certificates
Installation sheet
Other EU certificate
Other EU certificate
VMC_PR-2137/064_Conventional systems
Other EU certificate
VMC_232.303_NC-PF Panels
Other EU certificate
VMC_B-9212-FD-1103_NC-PFx
Technical documentation
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.