Skip to main content

DT2063N

ARITECH 2000 Series addressable heat detector
  • Dual thermistors
  • Remote signaling capabilities
  • Easy numeric addressing (1-128)
  • Enhanced communication protocol
  • Full diagnostic self testing
View all

At a glance

General

The DT2063N is a 2000 series protocol, addressable heat detector certified to class A2R. It provides good looks as well as top features, including a rate-of-rise algorithm that allows the device to raise the alarm before the fixed temperature trigger point is reached. Dual fire LEDs indicate an alarm visible from all directions, eliminating the need for special detector orientation on installation, whilst a remote indicator output is provided as standard on every device.

Installation friendly

The DT2063N is individually identified by setting an address through two rotary switches. The address is a straight numerical value and does not require binary or hexadecimal conversions, significantly reducing the risk of incorrect addressing.

All 2000 series detectors are compatible with a standard base that makes them easily interchangeable.

State of the art communication

Panel to device communication is provided through a powerful SIA protocol featuring multiple bus cycle codes and CRC error checking and ensuring reliable communications between the device and the control panel.

This enhanced protocol ensures the overall integrity and error free operation of the full system, without compromising speed.

Extended applications

For varied applications the fixed temperature trigger level of the DT2063N may be set from the CIE to accommodate higher activation temperatures.

A comprehensive line of complimentary devices completes the 2000 series portfolio:
· common use detector bases
· optical, temperature and multi-sensors
· standalone and base isolators
· sounder circuit controllers
· conventional zone monitoring units
· various supervised and non-supervised I/0 units
· a comprehensive line of manual call points
· loop powered notification devices and beam detectors

Details

  • Dual thermistors
  • Remote signaling capabilities
  • Easy numeric addressing (1-128)
  • Enhanced communication protocol
  • Full diagnostic self testing
  • Full range including optical and multi sensors
  • Full range of I/0 units and accessories
  • Optional isolator base
  • EN54:5 approved and CPR certified

Technical specifications

General
Status indication
Dual red alarm LED
User interface
LEDs
Compatibility
Aritech 2000 series systems
Alarm levels
5
Connectivity
2000 Series bases
Addressing method
Rotary switch
Electrical
Power supply type
Loop powered
Operating voltage
17 to 28 VDC
Current consumption
<270 µA (quiescent at 24 VDC)
4.7 mA (alarm at 24 VDC)
Detection
Detection principle
Heat
Monitoring
Alarm threshold
Sensitivity
Configurable
Coverage area
<80 m²
Air velocity
Unaffected
Alarm temperature (typical)
> +40°C
Rate-of-rise
Class A2
Output
Output quantity
1
Output type and rating
Remote indicator
Programmable
No
Remote alarm output
4.7 mA
Physical
Physical dimensions
100 x 50 mm (Ø x H)
Net weight
83 g
Colour
Cloud white (RAL 9001)
Mounting type
Ceiling mount
Material (body)
Plastic
Environmental
Vandal proof
No
Operating temperature
−10 to +50ºC
Storage temperature
-10 to +70°C
Application temperature (typical)
+25°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP20
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-5