Skip to main content

1-23911-K069

FireBeta XT Extinguishing Control Panel (3 Zone / 1 Area)
  • EN12094-1, EN54-2 and EN54-4 approved
  • Three detection zones as standard
  • Any single zone or any combinations of zones can be configured to release
  • Configurable first stage sounder delays
  • Configurable detection delays
View all

At a glance

General

FireBeta XT extinguishing control panels are designed and manufactured to the highest standards in a quality controlled environment. With it's EN12094-1 approvals it offers outstanding value and performance for small to medium sized fixed firefighting installations. The FireBeta XT is supplied in an enclosure that matches the design and colour of the status unit range.
The 3 detection zone circuits allow extinguishing agent release to be configured to activate from any combination of detection zones. This allows (among others) any 2 zones from the combination of 3 to activate release, making it ideal for applications protecting ceiling, room and floor voids.
The extensive configuration options of the FireBeta XT allow the functionality of the system to be extensively modified to suit the application while still complying with EN12094-1, EN54-2 and EN54-4. A large LED display on the panel fascia enables easy configuration and control. It additionally displays the time remaining until extinguishing agent release for added user safety.
The control panel status can be displayed on up to 7 remote status indicators. This allows the agent release status to be displayed at, for e.g. multiple entrances to a protected area, adding additional user safety. The communication between the panel and its status indicators is fully monitored.
The internal electronics are mounted on a single, easily removable steel plate making the FireBeta XT robust and easy to install.

Programmable functions

Access level 2:
▍ Test zones 1 to 3
▍ Disable zones 1 to 3
▍ Disable 1st stage alarms
▍ Disable pre-activated 1st stage relay
▍ Disable pre-activated 2nd stage relay
▍ Disable extract fan output
▍ Disable manual release input
▍ Disable extinguishant sub system
▍ Activate extract fan output
▍ Activate alarm delays
Access level 3:
▍ Sounder delay
▍ Coincidence detection
▍ Disable panel features
▍ Zone alarm delays (detectors)
▍ Zone alarm delays (manual call points)
▍ Configure zone for I.S. barrier use
▍ Zone short circuit alarm
▍ Zone non latching
▍ Zone inputs delay
▍ Extinguishant release time delay
▍ Extinguishant release duration timer
▍ Extinguishant reset delay timer

Details

  • EN12094-1, EN54-2 and EN54-4 approved
  • Three detection zones as standard
  • Any single zone or any combinations of zones can be configured to release
  • Configurable first stage sounder delays
  • Configurable detection delays
  • Zero time delay for manual release option
  • Compatible with I.S. barriers
  • Non-latching zone input option to receive signals from other systems e.g. aspiration systems
  • Configurable extinguishing agent delays up to 60 seconds in 5 second steps
  • Countdown timer shows time remaining until release
  • Supports up to seven, four wire status indicators
  • Built in extract fan control

Technical specifications

General
Status indicaton
LEDs
Compatibility
Status unit/Ancillary board connection
Connectivity
Two wire RS485
Communication ports
1
Maximum system capacity (device count)
up to 96
Network size (nodes)
up to 8
Electrical
Power supply type
230 VAC
Power consumption
100 W (max)
Operating voltage
28 VDC ±2 V
Current consumption
0.095 A
Mains supply fuse 1.6 A
Power supply rating 3 A
Maximum ripple 200 mV
Zone
Maximum zone capacity
up to 3
Quantity of devices per zone
32 (max) type dependent
Cable rating
0.5 mm² to 2.5 mm² solid or stranded wire, FP200 or equivalent
Quiescent current 2 mA (max.)
Termination 6k8 ½ W
Thresholds Normal, 8 to 1 kΩ
Thresholds Detector alarm, 999 to 400 Ω
Thresholds Manual call point alarm, 399 to 100 Ω
Thresholds Short circuit, 99 to 0 Ω
Input
Input quantity
4
Input type and rating
SIL, AL, FLT, RST switched -ve 100 Ω
Programmable
Yes
Termination
6k8 ½ W
Thresholds Normal, 8 to 1 kΩ
Thresholds Alarm, 999 to 100 Ω
Thresholds Short circuit, 99 to 0 Ω
Output
Output quantity
13
Output type and rating
Output specific
Fire alarm signalling
1 A @ 30 VDC
Fault signalling
1 A @ 30 VDC
Notification
500 mA @ 24 V
Auxilliary power
500 mA @ 24 V
Termination
Output specific
Output type and rating Local fire relay, 1 A @ 30 VDC
Output type and rating 1st stage relay, 1 A @ 30 VDC
Output type and rating 2nd stage relay, 1 A @ 30 VDC
Output type and rating Extract fan, 1 A @ 30 VDC
Output type and rating Extinguishing release, 1A
Extinguishing release delay 0 to 60 s (5 s steps)
Extinguishing release duration 60 to 300 s (5 s steps)
Termination Notification, 10 K ¼ W
Termination Extinguishing, 1N4004
Standby battery
Capacity
2 x 12 V, 7 Ah
Charging
0.7 A @ 27.6 VDC (temperature compensated)
Batteries supported in housing
2
Type Yuasa NP SLA
Battery fuse 3.15 A
Battery current 3 A (max.)
Physical
Form factor
Wall mount
Physical dimensions
385 x 310 x 90 mm
Net weight
6 kg
Colour
Grey
Mounting type
Wall mount
Material Mild sheet steel (1.2 mm)
Finish Epoxy powder coated
Terminal capacity 12 AWG
Environmental
Vandal proof
No
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
REACH
RoHS 2
WEEE
Certification
EN12094-1
EN54-2
EN54-4