Skip to main content

1-23911-K116

FireBeta A-XT Extinguishing Control Panel
  • UL864 and FM listed
  • Three initiation circuits as standard
  • Any single zone or any combinations of zones can be configured to release
  • Configurable first stage NAC delays
  • Configurable detection delays
View all

At a glance

General

The FireBeta A-XT UL/FM listed extinguishing control panel is designed and manufactured to the highest standards in a quality controlled environment. With UL and FM approvals it offers outstanding value and performance for small to medium sized fixed firefighting installations. FireBeta A-XT is supplied in a red enclosure.
The 3 initiation circuits allow extinguishant release to be configured to activate from any combination of detection zone inputs. This allows (among others) any 2 zones from the combination of 3 to activate release, making it ideal for applications protecting ceiling, room and floor voids.
The extensive configuration options of the FireBeta A-XT allow the functionality of the system to be extensively modified. A large LED display on the panel fascia enables easy configuration and control. It additionally displays the time remaining until extinguishing agent release for added user safety.
The countdown timer may be duplicated on up to 7 remote status units to provide local indication of the system status. This allows the agent release status to be displayed at, for e.g. multiple entrances to a protected area, adding additional user safety. The communication between the panel and its status indicators is fully monitored.
The internal electronics are mounted on a single, easily removable, steel plate making FireBeta A-XT panels both robust and easy to install.

Programmable Functions

Access Level 2
• Test Zones 1 to 3
• Disable Zones 1 to 3
• Disable 1st Stage Alarms
• Disable Pre-activated 1st Stage Relay
• Disable Pre-activated 2nd Stage Relay
• Disable Extract Fan Output
• Disable Manual Release Input
• Disable Releasing Sub System
• Activate Extract Fan Output
• Activate Alarm Delays
Access Level 3
• Sounder Delay
• Coincidence Detection
• Disable Panel Features
• Zone Alarm Delays (Detectors)
• Zone Alarm Delay (Call stations)
• Configure Zone for I.S Barrier Use
• Zone Short Circuit Alarm
• Zone Non Latching
• Zone Inputs Delay
• Extinguishant Release Time Delay
• Extinguishant Release Duration Timer
• Extinguishant Reset Delay Timer

Details

  • UL864 and FM listed
  • Three initiation circuits as standard
  • Any single zone or any combinations of zones can be configured to release
  • Configurable first stage NAC delays
  • Configurable detection delays
  • Zero time delay upon manual release option
  • Compatible with I.S. barriers
  • Non-latching zone input option to receive signals from other systems such as aspirating equipment
  • Configurable releasing delays up to 60 seconds in 5 second steps
  • Configurable releasing duration up to 5 minutes in 5 second steps
  • Countdown timer shows time remaining to release
  • Supports up to seven, four wire status indicators
  • Built in extract fan control

Technical specifications

General
Status indicaton
LEDs
Compatibility
Status unit/Ancillary board connection
Connectivity
Two wire RS485
Communication ports
1
Maximum system capacity (device count)
up to 96
Network size (nodes)
up to 8
Electrical
Power consumption
100 W (max)
Operating voltage
28 VDC ±2 V
Current consumption
0.095 A
Power supply type 115/230 VAC
Mains supply fuse 1.6 A (F1.6A L250V)
Power supply rating 3 A
Maximum ripple 200 mV
Zone
Maximum zone capacity
up to 3
Quantity of devices per zone
32 (max) type dependent
Quiescent current 2 mA (max)
Termination 6k8 ½ W
Thresholds Normal, 8 to 1 kΩ
Thresholds Detector alarm, 999 to 400 Ω
Thresholds Manual call point alarm, 399 to 100 Ω
Thresholds Short circuit, 99 to 0 Ω
Input
Input quantity
4
Input type and rating
SIL, AL, FLT, RST switched -ve 100 Ω
Termination
6k8 ½ W
Thresholds Normal, 8 to 1 kΩ
Thresholds Alarm, 999 to 100 Ω
Thresholds Short circuit, 99 to 0 Ω
Output
Output quantity
13
Output type and rating
Output specific
Fire alarm signalling
1 A @ 30 VDC
Fault signalling
1 A @ 30 VDC
Notification
500 mA @ 24 V
Auxilliary power
500 mA @ 24 V
Programmable
Yes
Termination
Output specific
Output type and rating ROV, 500 mA
Output type and rating Local fire relay, 1 A @ 30 VDC
Output type and rating 1st stage relay, 1 A @ 30 VDC
Output type and rating 2nd stage relay, 1 A @ 30 VDC
Output type and rating Extract fan, 1 A @ 30 VDC
Output type and rating Extinguishing release, 1A
Extinguishing release delay 0 to 60 s (5 s steps)
Extinguishing release duration 60 to 300 s (5 s steps)
Termination Notification, 10K ¼ W
Termination Extinguishing, 1N4004
Standby battery
Capacity
2 x 12 V, 7 Ah
Charging
0.7 A @ 27.6 VDC (temperature compensated)
Batteries supported in housing
2
Type Yuasa NP SLA
Battery fuse 3.15 A, glass, 20 mm
Battery current 3 A (max)
Physical
Form factor
Wall mount
Physical dimensions
368 x 310 x 90 mm
Colour
Red
Mounting type
Wall mount
Material Mild sheet steel (1.2 mm)
Finish Epoxy powder coated
Terminal capacity 12 AWG
Environmental
Vandal proof
No
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
UL
Certification
FM
UL
Standards
UL864

Downloads

All downloads

Datasheet

If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.