Gå til hovedindhold

9-30780-EN

AirSense ModuLaser, Minimum Display Module
  • Modular Design :
    Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap.
  • Zoned aspirating smoke detection :
    Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module.
  • Simplified installation :
    Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit.
  • Easy pipe connection :
    The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal.
  • Quick location of smoke :
    Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present.
Se alle

Overblik

General

ModuLaser is a scalable aspirating smoke detection solution that makes installation easier, maintenance quicker, and takes applications further than traditional air sampling detectors. Two basic module types comprise the ModuLaser solution: a display module, and a detector module. Each detector module can accommodate up to 250 meters combined sampling pipe. Display modules and detector modules communicate by RS-485 interconnections.
Display modules are available in three configurations: Standard with TFT color display, status LED's and navigation buttons, Minimum with only status LED's, and Command which is similar to the Standard but with the added functionality to control various modules over SenseNET. The Minimum and Standard Display Modules can each support up to 8 detector modules, while the Command Display Module can support up to 127 modules across the SenseNET network.

Minimum display module

The ModuLaser Minimum Display Module offers a cost effective alternative to the Standard Display Module. While the Standard Display Module features a user interface which consist of a TFT color display, navigation buttons and status LED’s, the Minimum Display Module only features status LED’s. Depending on the requirements of the installation, only having status LED’s might be sufficient to locally indicate faults or alarms while still reporting faults and alarms via the relay outputs or APIC. Due to the absence of a screen and navigation buttons, the Minimum Display Module(and associated detectors modules) must be configured via a computer using Remote software or via SenseNET using a Command Display Module.

Perfect solution

Thanks to advanced features that make it virtually impervious to dust and dirt, ModuLaser is ideal for use in hostile environments that would disable other kinds of smoke detectors. Forward scattering optical detection adds early warning capability without the risk of nuisance alarms normally associated with high sensitivity smoke detection, while exclusive environmental compensation technology adds a high degree of reliability to an already solid detection solution.

Detaljer

  • Modular Design : Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap.
  • Zoned aspirating smoke detection : Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module.
  • Simplified installation : Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit.
  • Easy pipe connection : The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal.
  • Quick location of smoke : Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present.
  • Universal Status LEDs

Tekniske specifikationer

General
Status indication
LED's
User interface
Navigation buttons
Alarm levels
4, Aux, Pre-alarm, Alarm and Alarm 2
Event log
20 000 events per module
RS485 support
Yes (SenseNET and SenseNET+)
Connectivity
USB (x2), IP and APIC on Display Module
Electrical
Operating voltage
18 to 30 VDC
Current consumption
Display Module (at 24 VDC): 204 mA (Minimum), 232 mA (Standard), 232 mA (Command)
Detector Module (at 24 VDC): 260 mA (fan speed 1), 380 mA (fan speed 6, default), 940 mA (fan speed 16)
Detection
Detection principle
Laser light scattering mass detection and particle evaluation
Particle sensitivity range
0.003 to 10 microns
Sampling pipe
Length
Up to 250 m (820 ft.) combined per detector module
Quantity sampling holes
Up to 20 - Class A per detector module
Up to 40 - Class B per detector module
Up to 50 - Class C per detector module
Inlet quantity
1
Inlet size
27 or 25 mm (1.06 or 0.98 in) outer diameter
Inlet location
Top or bottom
Exhaust size
27 or 25 mm (1.06 or 0.98 in) outer diameter
Exhaust location
Top or bottom
Inlet quantity 1 per detector module
Input
Input quantity
2 per module
Input type and rating
Supervised
Termination
15 KΩ 5% 1/4 W
Programmable
Yes
Output
Output quantity
3 per module
Output type and rating
Voltage free (contact rating 2 A at 30 VDC / NO/NC/C)
Programmable
Yes
Physical
Physical dimensions
110.5 x 133.5 x 300 mm (W x D x H)
(4.35 x 5.25 x 11.8 in) (W x D x H)
Net weight
Display Module:  1.18 Kg (2.6 lb.)
Detector Module:  1.57 Kg (3.46 lb.)
Colour
Grey-white (RAL 9002)
Mounting type
Surface mount
Cable entries
2 at the bottom, 2 at the rear, 2 at the top on Detector Module, and 3 at the top on the Display Module
Cable entry size 20 mm (0.5 in), top and bottom
Detector module orientation Vertical, 0 or 180°
Environmental
Operating temperature
Equipment:
-10 to +60°C (14 to +140°F)
Sampled air:
-20 to +60 °C (-4 to +140 °F)
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP40
Regulatory
Compliancy
REACH
RoHS
Certification
BOSEC
CPR
EN54-20
Chart recorder
Sampling period Adjustable between 1 s and 60 s
Capacity 1 months @ 1 s / Up to 5 years @ 60 s
Values recorded Detector value, 4 alarm level values, flow value and temperature (all simultaneously)