Gå til hovedindhold

NC-PX3

Conventional Fire and Extinguishing Panel - 3 Zone
  • Modern, elegant design with basic and intuitive user interface with icons.
  • Easy removable parts for quick and easy installation
  • Normal & head-out supervision support per zone
  • Three detection zones
  • Single zone, double zone or any combination of zones configurable for release
Se alle

Overblik

Overview

The New Conventional fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. With their clean and attractive contemporary design, they fits with any decor. The basic and intuitive user interface with icons make easy their application everywhere.

With support for multiple lines of conventional detectors and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.

The Panel

The NC-PX3 is a conventional fire alarm and extinguishing control panel. It is supplied in local language with 3 fire zones that support up to 32 devices per zone. These zones may be configured for extinguishing in single zone or double zone configuration in any combination of zones. In addition the panel offers supervised outputs for first stage notification, second stage notification as well as optical warning indicators and actuator activation. Standard relay outputs are provided for EN54 compliance and system status notification, as well as multiple inputs for system control.

Options

The panels support 2 types of auxiliary relay boards, one with 4 standard relays, and one with 4 supervised relays. With these boards the panel outputs may be expanded with up to 16 additional outputs.

Approvals & Compliance

The product line carries the following accreditations:

• EN54:2, EN54:4 and CE approved
• CPD certified
• EN12094-1 certified

• WEEE compliant
• RoHS compliant

Detaljer

  • Modern, elegant design with basic and intuitive user interface with icons.
  • Easy removable parts for quick and easy installation
  • Normal & head-out supervision support per zone
  • Three detection zones
  • Single zone, double zone or any combination of zones configurable for release
  • 6 Pre-configured relays and 8 supervised inputs for extinguishing control
  • Configurable fire routing, sounder, extinguishing, reset and door monitoring delays
  • Configurable "Hold Mode" type-A or type-B
  • Sounders configurable for pulsing or continuous operation
  • Extinguishing agent flow confirmation
  • Continuous or resetable 24 VDC auxiliary supply
  • Auxiliary standard & supervised relay output support
  • Default support for special functions such as: - EN54 compliant user access levels - Basic & Advanced level configuration - mixed zones - front panel diagnostics with test & disable control - one-man walk test

Tekniske specifikationer

General
Maximum system capacity (device count)
up to 96
Electrical
Power supply type
VAC
Power consumption
4 A @ 24 VDC
Operating voltage
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumption
3.15 A @ 110/1.5 A @ 240 VAC
2.78 A (Alarm, no devices)
0.39 A (Quiescent, no devices)
Loop
Maximum loop capacity
3
Zone
Maximum zone capacity
up to 3
Operating voltage
22 VDC (18 to 24 VDC)
Quantity of devices per zone
20 max.
Rating
65 mA (max. Load)
Cable rating
40 ohm (max. rsistance), 500 nF (max. capacitance)
Standby battery
Capacity
2 x 12 V, 12 Ah (SLA)
Physical
Form factor
Medium
Physical dimensions
440 x 480 x 140 mm (W x H x D)
Net weight
3.9 kg (without battery)
Shipping weight
6 kg
Colour
Grey (RAL 7035)
Mounting type
Surface mount
Cable entries
Ø 20 mm - 20 / 2 / 26 (top / bottom / rear)
Environmental
Operating temperature
-5 to +50°C
Storage temperature
-20 to +70°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
CPD
RoHS
WEEE
Certification
EN12094-1
EN54-13
EN54-2
EN54-4
Supervised Inputs
6
Use MCP Start, MCP Hold, MCP Abort, Pressure Switch, Gas Flow, Door Monitor
Non Supervised Inputs
2
Use Auto/Manual mode, Remote Reset
Supervised Outputs
4
Use Fire Sounders, Extinguishing Sounders, Optical Indications, Actuator
Notification 2 x 500 mA @ 24 VDC
Visual indictors 1 x 500 mA @ 24 VDC
Actuator 1 x 1 A @ 24 VDC
Non Supervised Outputs
4
Use Hold Mode, Abort Mode, Manual Mode, Release Indication
Specification 6 x 2 A @ 30 V
Auxilliary Supply Output
Output voltage 24 VDC (21 to 28 VDC)
Load (max) 250 mA