Gå til hovedindhold

KE-DP3121B-SNV

Excellence series intelligent addressable isolated dual optical/heat detector w/ sounder & VAD
  • Integrated loop short circuit isolation ensures operation during a loop overload
  • Short circuit isolation on remote indicator output for additional device protection
  • Nuisance alarm, steam & dust discrimination for superior false alarm immunity
  • Regular automatic self testing for operational piece of mind
  • Static and rate-of-rise temperature support
Se alle

Overblik

General

The innovative Excellence range of intelligent addressable devices offers advanced features for reliability and peace of mind. Coupled with features for ease of installation and maintenance on new fire detection systems, it’s a perfect match for exceptional overall performance.
The DP3121B-SNV is a Kidde Excellence series, graphite black addressable dual optical and heat detector with integrated short circuit isolation, sounder and VAD (Visual Alarm Device). It combines a low profile design with dual tri-colour status indication with 360° visibility. A remote indicator output is available to support a remote indicator up to 30 m away.
Detection reliability is ensured by combining dual optical wavelengths with multiple detection angles. This allows for state-of-the-art particle size detection that differentiates between real sources of alarm, or nuisance sources such as dust and steam. As a temperature detector, Class-A static and rate-of-rise modes are supported to further widen the application footprint.

Integrated notification

Every detector supports a freely programmable, audible and visual alarm device that can be independently controlled from the CIE. The sounder supports 32 alarm tones, each configurable at 4 alarm levels that allows complete customisation for the application and the alarm situation. The EN54-23 certified VAD offers 3 power ratings adding to full flexibility for management of loop loading on a system level.

User friendly

All detectors are individually identified by easily setting an address through 2, modern design rotary switches. The address is a directly identified number and does not require binary or hexadecimal conversions that significantly reduces the risk of incorrect addressing.

Installation & maintenance friendly

All Excellence series detectors are compatible with a standard base which makes installation planning seamless and detectors easily interchangeable. Self-testing and drift compensation ensure safe operation with contamination warnings provided when maintenance is needed.

Communication protocol

An enhanced protocol ensures the overall integrity and error-free operation of the system. The Excellence series protocol provides features like CRC error checking and multiple bus cycle codes to ensure reliability between panel and device communication. The Kidde Excellence protocol still support legacy 2000 series devices in combination with the Kidde Excellence series devices.

Detaljer

  • Integrated loop short circuit isolation ensures operation during a loop overload
  • Short circuit isolation on remote indicator output for additional device protection
  • Nuisance alarm, steam & dust discrimination for superior false alarm immunity
  • Regular automatic self testing for operational piece of mind
  • Static and rate-of-rise temperature support
  • Tri-colour indicators for alarm, pre alarm, isolation, fault, ItsMe and communications takes the guesswork out of operational status
  • 360° indicator visibility means no device alignment to ensure visibility
  • Easy mechanical rotary addressing
  • Event logging in the device for advanced diagnostics purposes
  • Supports 32 multi-stage tones at 4 alarm levels up to 86 dB(A)
  • Supports visual alarm notification at 3 levels up to C-3-9

Tekniske specifikationer

General
Status indication
Tri-colour LED
Compatibility
Kidde Commercial Excellence Systems
Alarm levels
5
Event log
Available
Connectivity
Excellence series, standard base
Addressing method
Rotary switch
Electrical
Power supply type
Loop powered
Operating voltage
17 to 29 VDC
Communication voltage
4 to 11 V pulsed
Current consumption
< 40 mA (alarm at 24 VDC - notification level dependant)
500 µA (quiescent at 24 VDC)
Terminals
6
Detection
Detection principle
Optical light scatter, forward and backward / Heat
Monitoring
Alarm threshold
Contamination level
Fault
Sensitivity
Selectable
Coverage area
< 57 m²
Particle sensitivity range
0.1 to 0.25 dB/m ±20%
Alarm temperature (maximum)
+70°C
Alarm temperature (minimum)
+54°C
Rate-of-rise
Supported
Installation height
< 3 m
Heat class (per EN54) A2S / A2R
Test fires (to ISO 7240) TF1, TF2, TF3, TF4, TF5, TF8, TF9
Output
Output quantity
1
Output type and rating
Remote indicator
Programmable
No
Remote alarm output
<8 mA
Isolation
Type
Negative line break
Quantity per loop
≤128
Isolation voltage
14 to 15.5 VDC
Reconnect voltage
14 to 15.5 VDC
Loop current
5 mA (isolated)
Switch current
1.05 A (continuous) / 1.4 A (pulsed)
Leakage current
<1 mA
Series resistance
<0.08 Ω
Impedance requirements
≤32 devices between isolators
Physical
Physical dimensions
100 x 54 mm (Ø x H)
Net weight
205 g
Colour
Graphite black (RAL 9011)
Mounting type
Base mount
Material (body)
PC / ABS
Material (contacts)
Brass
Functional marking
Device type, Isolation
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Storage temperature
-30 to +75°C
Application temperature (maximum)
+50°C
Application temperature (typical)
+25°C
Relative humidity
10 to 93% noncondensing
Environment
Indoor
IP rating
IP21C
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Voluntary marks
BOSEC
Standards
EN54-3, EN54-5, EN54-7, EN54-17, EN54-23
Sounder
Output level 51 to 86 dB(A) - Tone dependent
Output level adjustment 4 levels
Frequency User selectable
Selectable tones 32
Synchronization Supported
No. of stages 3
VAD
Colour Red
Rating User selectable up to C-3-9
Floor coverage < 63 m²
Flash frequency 0.2 Hz (1 flash every 2 s)
Synchronization Supported